Troubleshooting can be carried out in whole or in part using these instructions. It is important that you only carry out troubleshooting where you have sufficient knowledge and experience, especially when troubleshooting where the unit is live. Acetec accepts no responsibility for personal injury or damage to property during troubleshooting in accordance with these instructions.
Alarm 17 Service alarm, Flashing 17 on the control panel.
This indication is not an error alarm but a reminder for service (filter change).
Receipt can be done in 3 ways:
- Press and hold button 2 for about 5 seconds (not available in all programme versions).
- Set parameter 7 to the ON position by: Pressing buttons 1 and 3 simultaneously until the number 1 appears on the control panel. Press button 3 until the number 7 is displayed. Press and hold button 1, now Of is displayed, continue holding button 1 and press button 3 once, now ON is displayed, release button 1 and press button 2 until the display window goes out.
- Press the acknowledgement button on the circuit board.