EvoControl Ventilation – MPO1 Display

Language:
en-GB
Models: A30T, A50CS, A60T, A70T

6.9 Residual heat

Post-heating is selected on parameter 240:

Av

  • No reheating.

Ext. electricity

  • External electric heating coil (0–10 volts), terminals 35 & 36.
  • Own electrical supply and working switch required.

Int. El

  • Internal electric heating battery.
  • Alt. external electric heating battery with on/off control.
  • Max load terminal 16-17, 230 Vac / 10 A.

water

  • Control signal (0–10 volts), terminals 35 & 36.
  • A 24 Vdc power supply for actuators is available at terminals 33 and 34.
  • Heating circulation pump, 230 Vac (max 10A), terminals 16 & 17.
  • A freezer sensor is required (accessory), terminals 47 & 48.

See wiring diagram.