105 Restrict Fan Control
Limits the control signal to the fans.
Set in the factory and normally does not need to be changed.
Fan capacity settings are not affected.
Example. Parameter 105 = 80%.
Parameter 112 = 50% => Output signal to fan = 0.80 * (50 – 20) + 20 = 44%
Parameter 113 = 60% => Output signal to fan = 0.80 * (60 – 20) + 20 = 52%
(20 is the minimum fan speed.)
106 Pulses per revolution
Specifies how many pulses per revolution the fan produces.
Set at the factory and does not need to be changed unless the fan is changed to another model.
110 - 119 Fan capacity
Setting of Fan speed setpoints (%) in different operating modes.