EvoControl Ventilation – MPO1 Display

Language:
en-GB
Models: A30T, A50CS, A60T, A70T

6.5.4 Standby operation / Emergency situation

In case of an A-alarm that normally stops the unit and Standby / Emergency mode activated in parameter 480, the unit's extract air fan continues to run.

Indicated by the display of “Standby” at the top of the control panel.

  • Supply air fan = Off.
  • Exhaust air fan = On (capacity according to factory settings in each operating mode in %).
  • Rotor = On.
  • Internal electric battery = Off.
  • For water coil = Normal regulation.