Alarm 7 Supply air fan AVC-02

Estimated reading time: approx. 2 mins.

Troubleshooting can be carried out in whole or in part using these instructions. It is important that you only carry out troubleshooting where you have sufficient knowledge and experience, especially when troubleshooting where the unit is live. Acetec accepts no responsibility for personal injury or damage to property during troubleshooting in accordance with these instructions.

Alarm 7 Supply air fan, Flashing 7 on the control panel

Switch off the power supply to the unit and wait at least 2 minutes

Open the unit hatch

Spinning fan wheel by hand to rotate easily without noise

Check for bearing faults or if impeller catches on inlet cone

Switch on power supply to unit

Press button 1 on the control panel to switch the unit to the lowest operating mode

NOTE! at low outdoor temperature, the supply air fan may be delayed 1 minute

Check parameter 91 via the control panel

Press buttons 1 and 3 simultaneously for about 2 seconds until the number 1 appears on the panel

Press button 3 until the number 91 appears on the panel

Press and hold button 1 to read the parameter value

The parameter value shall be 2 for A390T, A400S, A600ST and A900ST and 1 for all other units

Change parameter 91 if the value is incorrect according to the following instruction

Option 1 for control panel labelled AVC-02 Switch off power supply to the unit

Press and hold the release button on the circuit board and switch on the power supply at the same time

Press and hold the release button until 4 LEDs next to the release button light up alternately

Release the acknowledge button

Press button 3 until the number 91 appears on the panel

Hold down button 1 and simultaneously press button 3, set 2 for A390T, A400S, A600ST, A900ST and 1 for all other units

Release button 1

Press button 3 until the digit window goes out

Option 2 for control panel labelled acetec

Change parameter 91 as instructed in the leaflet in programming mode 2

Open both fan connectors (2 cross screws in the connector loc) and check the attachment of cables

Switch on power supply to unit

Measure in the connector closest to the fan between terminals A and B where there should be 230V AC voltage and between terminals C and D there should be between 2 to 10V NOTE! DC voltage

Also check that there is contact between E and terminal 13 on the circuit board

Switch off power supply to unit

Check cables on terminals 11 to 15 on the circuit board by pressing the orange button, check the stripping approx. 7-10 mm, twist together, press the orange button, reattach the cable and release the orange button to lock the cable.