Estimated reading time: approx. 1 min.

Troubleshooting can be carried out in whole or in part using these instructions. It is important that you only carry out troubleshooting where you have sufficient knowledge and experience, especially when troubleshooting where the unit is live. Acetec accepts no responsibility for personal injury or damage to property during troubleshooting in accordance with these instructions.

Alarm 3 Supply air temperature below 5 degrees, flashing 3 on the control panel.

Check that the reheating coil is not switched off, parameter 31 should be in the ON position.

Are airflows adjusted, measured by an adjustment expert?

The exhaust air flow should be slightly higher than the supply air flow. See brochure and parameter list, check parameters 11 to 18 which are fan settings. Are filters very dirty? Check special exhaust air filter and change if necessary.

At A70T, if basic flow in kitchen is taken via cooker hood, this leads to lower heat recovery and problems to keep the right supply air temperature at low outdoor temperature

Check the damper disc in the cooker hood by removing the filter, the damper disc should close tightly when the damper control closes the damper in the hood. There should be no opening in the damper disc, tape up the opening to urgently solve problems with low supply air temperature, basic flow in the kitchen should be taken via a separate exhaust air device and not via the cooker hood

Kommer larm vid hög utetemperatur? Byt svart relä på kretskort genom att lossa trådbygel.