The function is called Rotor test respectively De-icing and is activated automatically when required.
If no rotor pulses reach the main board for 30 seconds (4 minutes during defrosting and moisture reduction), carry out the steps below, depending on the current outdoor temperature.
Uteluftstemperatur över 0°C (rotortest)
- Indicated on the control panel by:
- AVC-02: rt
- EvoControl: Rotor test under ‘Measurement Values/Extra Operating Mode’
- The supply and extract air fans are operating as normal.
- The rotor stops for two minutes.
- The rotor runs continuously for one minute.
- If no pulses reach the control unit, steps c and d are repeated three times before the rotor alarm is triggered.
- If pulses are received by the control unit, the unit returns to normal control mode.
Uteluftstemperatur under 0°C (avisning)
- Indicated on the control panel by:
- AVC-02: rt / A which changes
- EvoControl: De-icing under ‘Measurement Values/Extra Operating Mode’
- Tilluftsfläkten stannar och frånluftsfläkten går med minst 50% kapacitet.
- The reheating coil is switched on.
- The rotor stops for 10 minutes.
- The rotor runs continuously for one minute.
- If no pulses reach the control unit, steps d and e are repeated three times before an alarm is triggered.
- If pulses are received by the control unit, a 30-minute defrost cycle is initiated before the unit returns to normal operation.
