WARNING – Electrical voltage
Contact with live parts may result in an electric shock, serious injury or death.
Stopping the unit via the control panel or control system does not de-energise it. Disconnect the mains supply and secure it against being switched on again before opening the electrical enclosure or carrying out any electrical work.
Åtgärden får endast utföras av personer som uppfyller de krav som anges för aktuell målgrupp i produktens bruksanvisning.
Troubleshooting can be carried out in whole or in part using these instructions. It is important that you only carry out troubleshooting where you have sufficient knowledge and experience, especially when troubleshooting where the unit is live. Acetec accepts no responsibility for personal injury or damage to property during troubleshooting in accordance with these instructions.
Indications: a flashing ‘3’ on the control panel.
Troubleshooting
- Switch off the power supply to the unit.
- Check that the supply air sensor is positioned in the supply air duct.
- Check the sensor cable between the sensor and the unit for any damage.
- Check the connection and stripping on terminals 41–42: press the orange button to release the cable and check that the stripped length is approx. 7–10 mm. Twist the wires together, press the orange button and reattach the cable.