6.19 Testing of units

Testing of unit inputs, outputs and parts can be done manually.

Go to settings and enter the authorisation code 123321.

Test parameters are displayed and they can be switched on and off and display values.

  • In case of control signal VVX, the heat exchanger also starts and runs in pulses after the control signal (-1 = 100%).
  • When a heating control signal is received, 230 Vac is also output at terminals 16 and 17.
  • When a ‘cool’ control signal is received, 230 Vac is also output at terminals 17 and 18.

See Parameter settings here.

To end the test, you must exit the menu by pressing Back.

You can enter test mode by pressing the button Advanced settings. Code.

Freeze protection is NOT active in “Test mode”.