EvoControl Ventilation Touch Display
Models: A100 G3, A110T G3-G4, A170T G2, A200S, A230T, A250S, A390T, A400S, A590T, A600S/T, A900ST G3, A1, A2, M1, M2, R20, R25, R40, R50, R70
Depending on the settings, not all parameters are always displayed!
Depending on the programme version, not all parameters are always available! Some functions/parameters require accessories! The minimum and maximum values of the parameters as well as the factory value may vary slightly depending on the programme version!
New parameter IDs for “Alarm clock” (ID 8000->) and “Alarms / Alarm history” (ID 9000->) with effect from 22 October 2024.
Explanation of column:
Id = Parameter id, used for communication with ModBus.
ModBus = ModBus register type (Input / Holding register).
Level = User level in display (0=all, 1=simple, 2=advanced).
Text values / ModBus = Explanation of a value.
| Id | Text | ModBus | Level | Min | Max | Text values / ModBus | Factory value | Unit |
|---|---|---|---|---|---|---|---|---|
| Fan | ||||||||
| 100 | Location Supply air fan | 4 | 2 | 0=Nedre (A1&A2=Höger), 1=Övre (A1&A2=Vänster) | 1=Upper | 0 | ||
| 105 | Restrict Fan Control | 4 | 2 | 30 | 100 | 0 | 100 | % |
| 106 | Pulses per lap | 0 | 2 | 1 | 10 | 0 | 1 | ppr |
| 110 | Fan speed Supply air Saving | 4 | 1 | 20 | 100 | 0 | 30 | % |
| 111 | Fan speed Exhaust air Saving | 4 | 1 | 20 | 100 | 0 | 40 | % |
| 112 | Fan speed Supply air Comfort | 4 | 1 | 20 | 100 | 0 | 45 | % |
| 113 | Fan speed Exhaust air Comfort | 4 | 1 | 20 | 100 | 0 | 60 | % |
| 114 | Fan speed Supply air Forcing | 4 | 1 | 20 | 100 | 0 | 60 | % |
| 115 | Fan speed Exhaust air Forcing | 4 | 1 | 20 | 100 | 0 | 80 | % |
| 116 | Fan speed Supply air External 1 | 4 | 1 | 20 | 100 | 0 | 45 | % |
| 117 | Fan speed Exhaust air External 1 | 4 | 1 | 20 | 100 | 0 | 60 | % |
| 118 | Fan speed Supply air External 2 | 4 | 1 | 20 | 100 | 0 | 45 | % |
| 119 | Fan speed Exhaust air External 2 | 4 | 1 | 20 | 100 | 0 | 60 | % |
| 130 | Pressurise Supply Air Save | 4 | 1 | 15 | 2000 | 0 | 20 | Pa |
| 131 | Pressure Exhaust air Saving | 4 | 1 | 15 | 2000 | 0 | 30 | Pa |
| 132 | Pressure Supply air Comfort | 4 | 1 | 15 | 2000 | 0 | 45 | Pa |
| 133 | Pressure Exhaust air Comfort | 4 | 1 | 15 | 2000 | 0 | 80 | Pa |
| 134 | Pressure Supply air Forcing | 4 | 1 | 15 | 2000 | 0 | 80 | Pa |
| 135 | Pressure Exhaust air Forcing | 4 | 1 | 15 | 2000 | 0 | 150 | Pa |
| 136 | Pressure Supply air External 1 | 4 | 1 | 15 | 2000 | 0 | 45 | Pa |
| 137 | Pressure Exhaust air External 1 | 4 | 1 | 15 | 2000 | 0 | 80 | Pa |
| 138 | Pressure Supply air External 2 | 4 | 1 | 15 | 2000 | 0 | 45 | Pa |
| 139 | Pressure Exhaust air External 2 | 4 | 1 | 15 | 2000 | 0 | 80 | Pa |
| 150 | Flow Supply air Saving | 4 | 1 | 10 | 10000 | 0 | 200 | l/s |
| 151 | Flow Exhaust air Savings | 4 | 1 | 10 | 10000 | 0 | 300 | l/s |
| 152 | Flow Supply air Comfort | 4 | 1 | 10 | 10000 | 0 | 450 | l/s |
| 153 | Flow rate Exhaust air Comfort | 4 | 1 | 10 | 10000 | 0 | 800 | l/s |
| 154 | Flow Supply air Forcing | 4 | 1 | 10 | 10000 | 0 | 800 | l/s |
| 155 | Flow Exhaust air Forcing | 4 | 1 | 10 | 10000 | 0 | 1500 | l/s |
| 156 | Flow rate Supply air External 1 | 4 | 1 | 10 | 10000 | 0 | 500 | l/s |
| 157 | Flow rate Exhaust air External 1 | 4 | 1 | 10 | 10000 | 0 | 1000 | l/s |
| 158 | Flow rate Supply air External 2 | 4 | 1 | 10 | 10000 | 0 | 500 | l/s |
| 159 | Flow rate Exhaust air External 2 | 4 | 1 | 10 | 10000 | 0 | 1000 | l/s |
| temperature | ||||||||
| 200 | Controller type | 4 | 1 | 0=On, 1=Off, 2=Auto, 3=FRT | 0=To | 0 | ||
| 201 | Switching temp Controller type | 4 | 1 | -10 | 10 | 0 | 5 | °C |
| 205 | Neutralzone Kyla | 4 | 2 | 1 | 10 | Decimal number | 2 | °K |
| 210 | Temperature Savings | 4 | 1 | 10 | 40 | 0 | 20 | °C |
| 211 | Temperature Comfort | 4 | 1 | 10 | 40 | 0 | 20 | °C |
| 212 | Temperature Forcing | 4 | 1 | 10 | 40 | 0 | 20 | °C |
| 213 | Temperature External 1 | 4 | 1 | 10 | 40 | 0 | 20 | °C |
| 214 | External temperature 2 | 4 | 1 | 10 | 40 | 0 | 20 | °C |
| 220 | Temperature Savings FRT | 4 | 1 | -5 | 5 | 0 | -2 | °K |
| 221 | Temperature Comfort FRT | 4 | 1 | -5 | 5 | 0 | -2 | °K |
| 222 | Temperature Forcing FRT | 4 | 1 | -5 | 5 | 0 | -2 | °K |
| 223 | Temperature External 1 FRT | 4 | 1 | -5 | 5 | 0 | -2 | °K |
| 224 | Temperature External 2 FRT | 4 | 1 | -5 | 5 | 0 | -2 | °K |
| 230 | Outdoor compensation at -20°C | 4 | 1 | -5 | 5 | 0 | 0 | °K |
| 231 | Outdoor compensation at 0°C | 4 | 1 | -5 | 5 | 0 | 0 | °K |
| 232 | Outdoor compensation at +40°C | 4 | 1 | -10 | 10 | 0 | 0 | °K |
| 240 | Residual heat | 4 | 1 | 0=Off, 1=Ext. Electricity, 2=Int. Electricity, 3=Water, 4=Mixed sign. | 2=Int. Elbatt | 0 | ||
| 241 | Hysteresis EVB | 4 | 2 | 0,5 | 2 | Decimal number | 1 | °K |
| 245 | Heat retention Water temp | 4 | 2 | 10 | 30 | 0 | 20 | °C |
| 246 | Freeze monitor Alarm limit | 4 | 2 | 5 | 15 | 0 | 7 | °C |
| 248 | Cooling signal | 4 | 1 | 0=Off, 1=On | 1=On | 0 | ||
| 250 | Preheating / Cooling pump / EvoCool | 4 | 1 | 0=Off, 1=Preheating, 2=Cooling pump, 3=EvoCool | 0=Off | 0 | ||
| 251 | Utetemp, Activation Preheating | 4 | 1 | -25 | 0 | 0 | -15 | °C |
| 260 | Supply air regulator P-band | 4 | 2 | 10 | 300 | 0 | 50 | °K |
| 261 | Supply air controller I-time | 4 | 2 | 20 | 600 | 0 | 100 | s |
| 262 | Minbegr Supply air temperature | 4 | 2 | 10 | 25 | 0 | 10 | °C |
| 263 | Maxbegr Supply air temperature | 4 | 2 | 15 | 50 | 0 | 40 | °C |
| 264 | Low temperature alarm Supply air | 4 | 2 | -20 | 15 | 0 | 5 | °C |
| 266 | High temperature alarm Post-heating | 4 | 2 | 1 | 10 | 0 | 4 | °K |
| 270 | Off/Room controller P-band | 4 | 2 | 1 | 300 | 0 | 4 | °K |
| 271 | Off/Room controller I-time | 4 | 2 | 10 | 1800 | 0 | 300 | s |
| 272 | Off/Rum cascade factor | 4 | 2 | 2 | 10 | 0 | 5 | °K |
| 273 | Low temperature alarm Exhaust air | 4 | 2 | -20 | 15 | 0 | 10 | °C |
| Extra credit | ||||||||
| 300 | Humidity sensor | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 301 | Setpoint Moisture | 4 | 1 | 20 | 90 | 0 | 60 | % |
| 302 | Capacity increase Moisture management | 4 | 1 | -20 | 100 | 0 | 30 | % |
| 303 | Coupling diff Humidity control | 4 | 2 | 3 | 15 | 0 | 5 | % |
| 304 | Control signal VVX for humidity control | 4 | 2 | 10 | 100 | 0 | 70 | % |
| 310 | Pressure sensor Supply air | 4 | 1 | 0=Off, 1=Pressure, 2=Flow, 3=Slave, 4=Measured pressure, 5=Measured flow. flow | 0=Off | 0 | ||
| 311 | Pressure sensor Exhaust air | 4 | 1 | 0=Off, 1=Pressure, 2=Flow, 3=Slave, 4=Measured pressure, 5=Measured flow. flow | 0=Off | 0 | ||
| 312 | Pressure sensor Measuring range | 4 | 2 | 100 | 2500 | 0 | 300 | Pa |
| 313 | Slave control Diff | 4 | 1 | -50 | 50 | 0 | 0 | % |
| 314 | K-factor | 4 | 2 | 1 | 1000 | Decimal number | 40 | 0 |
| 315 | Pressure control P-Band / Setpoint | 4 | 2 | 2 | 50 | Decimal number | 10 | 0 |
| 316 | Pressure regulation I-Tid | 4 | 2 | 20 | 300 | 0 | 30 | s |
| 317 | Pressure control Alarm limit deviation +- | 4 | 2 | 5 | 50 | 0 | 20 | % |
| 330 | Air quality sensor | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 331 | Air quality sensors Measuring range | 4 | 2 | 20 | 2000 | 0 | 2000 | ppm |
| 332 | Air quality Setpoint | 4 | 1 | 2 | 2000 | 0 | 800 | ppm |
| 333 | Air quality Coupling diff | 4 | 1 | 2 | 400 | 0 | 150 | ppm |
| Features | ||||||||
| 400 | ECO mode | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 401 | ECO temperature | 4 | 2 | 10 | 40 | 0 | 17 | °C |
| 410 | Hot start Temp | 4 | 1 | -20 | 20 | 0 | 5 | °C |
| 411 | Hot start Time | 4 | 1 | 0 | 5 | 0 | 2 | m |
| 420 | Fire function | 4 | 2 | 1 | 4 | 0 | 1 | 0 |
| 430 | Forced cooling | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 431 | Increase in cooling capacity | 4 | 2 | 0 | 100 | 0 | 30 | % |
| 435 | Refrigeration recovery | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 436 | Cooling recovery Diff temp | 4 | 2 | 1 | 5 | 0 | 2 | °K |
| 440 | Free cooling via outdoor air | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 441 | Free cooling at outdoor air temperature | 4 | 2 | 0 | 25 | 0 | 10 | °C |
| 442 | Free cooling at exhaust air temperature | 4 | 2 | 15 | 30 | 0 | 25 | °C |
| 450 | Defrosting | 4 | 1 | 0=Off, 1=On (All aggregates smaller than A390T are default=On) | 0=Off | 0 | ||
| 451 | Defrosting Starts at Utetemp | 4 | 2 | -30 | 0 | 0 | -10 | °C |
| 452 | Defrosting time | 4 | 2 | 2 | 30 | 0 | 20 | m |
| 453 | Defrosting interval | 4 | 2 | 30 | 600 | 0 | 180 | m |
| 454 | VVX Control | 4 | 2 | 0=Off, 1=On | 1=On | 0 | ||
| 455 | Winter drift | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 456 | Winter operation Starts at Utetemp | 4 | 2 | -20 | 10 | 0 | -5 | °C |
| 457 | Winter operation Fan Supply air | 4 | 2 | -50 | 50 | 0 | -20 | % |
| 458 | Winter operation Fan Exhaust air | 4 | 2 | -50 | 50 | 0 | 20 | % |
| 459 | Winter operation Moisture reduction Rotor | 4 | 2 | 0 | 100 | In case of moisture reduction, the residual value is 60% | 0 | % |
| 460 | Overpressure timer Time | 4 | 1 | 0 | 30 | 0 | 15 | m |
| 461 | Forcing hours Time | 4 | 1 | 0 | 240 | 0 | 120 | m |
| 465 | Presence, Switch-off delay | 4 | 2 | 0 | 72 | 0=Off | 0 | h |
| 466 | Presence, Operating mode | 4 | 2 | 0=External Economy, 1=External Comfort, 2=External Forced, 3=External 1, 4=External 2 |
1=External comfort | 0 | ||
| 467 | Presence, Operating mode Return | 4 | 2 | 0=Standby, 1=Stop, 2=Save, 3=Comfort, 4=Forced, 5=Time | 2=Savings | 0 | ||
| 470 | Order of priority, External Entrances | 4 | 2 | 0=Prime, 1=Last | 0=Prio | 0 | ||
| 471 | Prioritisation, External Stop | 4 | 2 | 0=Prime, 1=Last | 0=Prio | 0 | ||
| 472 | Prioritisation, External Fire | 4 | 2 | 0=Prime, 1=Last | 0=Prio | 0 | ||
| 475 | Engine type | 0 | 2 | 0=Induction motor, 1=Stage motor (on/off), 2=Stage motor N17, 3=Stage N24 engine |
0=Induction motor | 0 | ||
| 476 | Stepper motor, Max shaft speed | 0 | 2 | 20 | 400 | 0 | 90 | rpm |
| 477 | Stepper motor, Current | 0 | 2 | -10 | 10 | 0 | 0 | 0 |
| 478 | Stepper motor, Direction | 0 | 2 | 0=CW, 1=CCW | 0=CW | 0 | ||
| 480 | Standby Operation | 4 | 1 | 0=Off, 1=On | 1=On | 0 | ||
| 482 | Exercise driving | 4 | 2 | 0=Off, 1=On | 1=On | 0 | ||
| Button lock | ||||||||
| 500 | stop | 4 | 1 | 0=Off, 1=On | 0=Off | |||
| 501 | Spruce | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 502 | Comfort and convenience | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 503 | Forced | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 504 | Tidur | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 505 | Overpressure | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 506 | Forced timer | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 507 | ECO | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 508 | temperature | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 520 | Timer setting | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 521 | Alarm management | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| Alarm settings | ||||||||
| 900 | Communication Disp. | 4 | 2 | Id 1, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 2=B-alarm | 0 | ||
| 901 | Alarm delay, P900 | 4 | 2 | 30 | 6000 | 0 | 60 | s |
| 902 | Network, TCP/IP | 4 | 2 | Id 2, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 3=C-alarm | 0 | ||
| 903 | Alarm delay, P902 | 4 | 2 | 60 | 6000 | 0 | 600 | s |
| 904 | Internet connection | 4 | 2 | Id 3, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 3=C-alarm | 0 | ||
| 905 | Alarm delay, P904 | 4 | 2 | 60 | 6000 | 0 | 600 | s |
| 906 | Cloud service | 4 | 2 | Id 4, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 3=C-alarm | 0 | ||
| 907 | Alarm delay, P906 | 4 | 2 | 60 | 6000 | 0 | 600 | s |
| 908 | Fan Supply air | 4 | 2 | Id 5, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 909 | Alarm delay, P908 | 4 | 2 | 10 | 600 | 0 | 30 | s |
| 910 | Fan Exhaust air | 4 | 2 | Id 6, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 911 | Alarm delay, P910 | 4 | 2 | 10 | 600 | 0 | 30 | s |
| 912 | Heat exchangers | 4 | 2 | Id 7, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 913 | Alarm delay, P912 | 4 | 2 | 30 | 600 | 0 | 60 | s |
| 914 | Freeze alarm Return circuit | 4 | 2 | Id 8, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 915 | Alarm delay, P914 | 4 | 2 | 5 | 30 | 0 | 5 | s |
| 916 | Low supply air temperature | 4 | 2 | Id 9, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 917 | Alarm delay, P916 | 4 | 2 | 60 | 6000 | 0 | 6000 | s |
| 918 | Low Exhaust air temp | 4 | 2 | Id 10, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 0=Off | 0 | ||
| 919 | Alarm delay, P918 | 4 | 2 | 60 | 6000 | 0 | 6000 | s |
| 920 | Supply Air Temperature Sensor | 4 | 2 | Id 11, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 921 | Alarm delay, P920 | 4 | 2 | 5 | 30 | 0 | 5 | s |
| 922 | Exhaust air temperature sensor | 4 | 2 | Id 12, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 923 | Alarm delay, P922 | 4 | 2 | 5 | 30 | 0 | 5 | s |
| 924 | Outdoor Air Temperature Sensor | 4 | 2 | Id 13, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 925 | Alarm delay, P924 | 4 | 2 | 5 | 30 | 0 | 5 | s |
| 926 | Temp sensor Freeze guard | 4 | 2 | Id 14, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 1=A alarm | 0 | ||
| 927 | Alarm delay, P926 | 4 | 2 | 5 | 30 | 0 | 5 | s |
| 928 | Humidity sensor | 4 | 2 | Id 15, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 2=B-alarm | 0 | ||
| 929 | Alarm delay, P928 | 4 | 2 | 30 | 6000 | 0 | 60 | s |
| 930 | Pressure value Supply air | 4 | 2 | Id 16, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 2=B-alarm | 0 | ||
| 931 | Alarm delay, P930 | 4 | 2 | 60 | 6000 | 0 | 600 | s |
| 932 | Pressure value Exhaust air | 4 | 2 | Id 17, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 2=B-alarm | 0 | ||
| 933 | Alarm delay, P932 | 4 | 2 | 60 | 6000 | 0 | 600 | s |
| 934 | fire | 4 | 2 | Id 18, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 3=C-alarm | 0 | ||
| 935 | Alarm delay, P934 | 4 | 2 | 5 | 30 | 0 | 5 | s |
| 936 | High Reheat Temp | 4 | 2 | Id 19, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 2=B-alarm | 0 | ||
| 937 | Alarm delay, P936 | 4 | 2 | 600 | 9000 | 0 | 5400 | s |
| 944 | Communication Stegm. | 4 | 2 | Id 23, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 2=B-alarm | 0 | ||
| 945 | Alarm delay, P944 | 4 | 2 | 30 | 6000 | 0 | 60 | s |
| Mixed | ||||||||
| 1000 | Rotor | 3 | 100 | 0=Off, 1=On | 0=Off | 0 | ||
| 1001 | Heating | 3 | 100 | 0=Off, 1=On | 0=Off | 0 | ||
| 1002 | Kyla | 3 | 100 | 0=Off, 1=On | 0=Off | 0 | ||
| 1003 | Alarm | 3 | 100 | 0=Off, 1=A alarm, 2=B alarm, 3=C alarm | 0=Off | 0 | ||
| 1004 | Cloud service | 3 | 100 | 0=Off, 1=Not connected, 2=Connected, 3=Remote, 4=Remote time | 0=Off | 0 | ||
| 1005 | Network, TCP/IP | 3 | 100 | 0=Off, 1=No cable, 2=Connected, 3=Internet | 0=Off | 0 | ||
| 1010 | Fashion rules | 4 | 1 | 0=Standby, 1=Stop, 2=Save, 3=Comfort, 4=Forced, 5=Overpressure, 6=Forced Time, 7=External Fire, 8=External Stop, 9=External Save, 10=External Comfort, 11=External Forced, 12=External 1, 13=External 2, 14=Time Off, 15=Time Saving, 16=Time Comfort, 17=Time Forced, 18=Tidur External 1, 19=Tidur External 2, 20=Tidur Spar AirQ, 21=Tidur Comf. AirQ, 22=Tidur Forc. AirQ |
1=Stop | 0 | ||
| 1015 | Special rules mother | 3 | 100 | 0=Off, 1=Defrosting, 2=Warming, 3=Freeze protection, 4=Refrigeration recovery, 5=Free cooling, 6=Reserve operation, 7=Moisture reduction, 8=Winter operation, 9=Display, 10=Root test, 11=Start-up, 12=Attendance |
0=Off | 0 | ||
| 1016 | Tidur | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 1017 | ECO | 4 | 1 | 0=Off, 1=On | 0=Off | 0 | ||
| 1021 | Date of last service | 4 | 1 | -1 | 2147483647 | -1=Service not done | -1 | Epoch |
| 1022 | (ModBus) | 4 | 1 | 0 | 0 | 0 | ||
| 1023 | Service interval | 4 | 1 | 0 | 36 | 0 | 12 | m |
| 1024 | Days to next service | 3 | 100 | -1 | 99999 | -1=Time for service | -1 | d |
| Measurement values | ||||||||
| 1100 | Drift mode | 3 | 0 | 0=Standby, 1=Stop, 2=Save, 3=Comfort, 4=Forced, 5=Overpressure, 6=Forced Time, 7=External Fire, 8=External Stop, 9=External Save, 10=External Comfort, 11=External Forced, 12=External 1, 13=External 2, 14=Time Off, 15=Time Saving, 16=Time Comfort, 17=Time Forced, 18=Tidur External 1, 19=Tidur External 2, 20=Tidur Spar AirQ, 21=Tidur Comf. AirQ, 22=Tidur Forc. AirQ |
1=Stop | 0 | ||
| 1101 | Extra operating mode | 3 | 0 | 0=Off, 1=Defrosting, 2=Warming, 3=Freeze protection, 4=Refrigeration recovery, 5=Free cooling, 6=Reserve operation, 7=Moisture reduction, 8=Winter operation, 9=Display, 10=Root test, 11=Start-up, 12=Attendance |
0=Off | 0 | ||
| 1110 | Supply air temperature | 3 | 0 | -50 | 70 | Decimal number | 0 | °C |
| 1111 | Exhaust air temperature | 3 | 0 | -50 | 70 | Decimal number | 0 | °C |
| 1112 | Outdoor air temperature | 3 | 0 | -50 | 70 | Decimal number | 0 | °C |
| 1113 | Return temperature Water | 3 | 0 | -50 | 70 | Decimal number | 0 | °C |
| 1120 | Moisture sensor Moisture content | 3 | 0 | 0 | 100 | 0 | 0 | % |
| 1121 | Humidity sensor Temperature | 3 | 0 | -50 | 150 | Decimal number | 0 | °C |
| 1130 | Air quality | 3 | 0 | 0 | 2000 | 0 | 0 | ppm |
| 1140 | Rotor Speed | 3 | 0 | 0 | 100 | Decimal number | 0 | rpm |
| 1142 | Rotor Efficiency | 0 | 0 | -1 | 100 | Only when reheat=Off. (((Temp TL - Temp UL) / (Temp FL - Temp UL)) * 100) |
-1 | % |
| 1150 | Supply air Fan control signal | 3 | 0 | 0 | 100 | 0 | 0 | % |
| 1151 | Supply air Fan speed | 3 | 0 | 0 | 20000 | 0 | 0 | rpm |
| 1152 | Supply air Pressure | 3 | 0 | 0 | 5000 | 0 | 0 | Pa |
| 1153 | Supply air Air flow | 3 | 0 | 0 | 30000 | 0 | 0 | l/s |
| 1160 | Extract air Fan control signal | 3 | 0 | 0 | 100 | 0 | 0 | % |
| 1161 | Exhaust air Fan speed | 3 | 0 | 0 | 20000 | 0 | 0 | rpm |
| 1162 | Exhaust air Pressure | 3 | 0 | 0 | 5000 | 0 | 0 | Pa |
| 1163 | Exhaust air Air flow | 3 | 0 | 0 | 30000 | 0 | 0 | l/s |
| 1170 | Control signal Heat recovery | 3 | 0 | 0 | 100 | 0 | 0 | % |
| 1171 | Control signal Heat | 3 | 0 | 0 | 100 | 0 | 0 | % |
| 1172 | Cooling control signal | 3 | 0 | 0 | 100 | 0 | 0 | % |
| 1180 | Electric battery | 3 | 0 | 0=Off, 1=On | 0=Off | 0 | ||
| 1181 | Preheating | 3 | 0 | 0=Off, 1=On | 0=Off | 0 | ||
| 1182 | Circulation pump Heating | 3 | 0 | 0=Off, 1=On | 0=Off | 0 | ||
| 1183 | Circulation pump Kyla | 3 | 0 | 0=Off, 1=On | 0=Off | 0 | ||
| 1200 | Operating time Aggregate | 3 | 0 | 0 | 2147483647 | 0 | 0 | h |
| 1201 | (ModBus) | 3 | 0 | 0 | 0 | 0 | ||
| 1202 | Total Power output VVX | 3 | 0 | 0 | 2147483647 | 0 | 0 | % |
| 1203 | (ModBus) | 3 | 0 | 0 | 0 | 0 | ||
| 1204 | Total Power output Post-heating | 3 | 0 | 0 | 2147483647 | 0 | 0 | % |
| 1205 | (ModBus) | 3 | 0 | 0 | 0 | 0 | ||
| 1206 | Total Power output Cooling | 3 | 0 | 0 | 2147483647 | 0 | 0 | % |
| 1207 | (ModBus) | 3 | 0 | 0 | 0 | 0 | ||
| 1208 | Operating time Int. Electric battery | 3 | 0 | 0 | 2147483647 | 0 | 0 | h |
| 1209 | (ModBus) | 3 | 0 | 0 | 0 | 0 | ||
| Display | ||||||||
| 5100 | Language | 4 | 1 | 0=Swedish, 1=English | 0=Swedish | 0 | ||
| 5110 | Display Brightness | 4 | 1 | 10 | 100 | 0 | 100 | % |
| 5111 | Screen saver | 4 | 1 | 0=Off, 1=Logo | 1=Logo | 0 | ||
| 5120 | Time zone GMT | 4 | 1 | 0 | 2 | 0 | 1 | 0 |
| 5121 | Set time | 4 | 1 | -2147483647 | 2147483647 | Automatically resets to 0 | 0 | Epoch |
| 5122 | (ModBus) | 4 | 1 | 0 | 0 | 0 | ||
| Help for display | ||||||||
| 5130 | Year | 0 | 1 | 1970 | 2038 | 0 | 2025 | 0 |
| 5131 | Month | 0 | 1 | 0=January, 1=February, 2=March, 3=April, 4=May, 5=June, 6=July, 7=August, 8=September, 9=October, 10=November, 11=December |
0=January | 0 | ||
| 5132 | Day | 0 | 1 | 1 | 31 | 0 | 1 | 0 |
| 5133 | Hour | 0 | 1 | 0 | 23 | 0 | 0 | 0 |
| 5134 | minute | 0 | 1 | 0 | 59 | 0 | 0 | 0 |
| 5135 | Second | 0 | 1 | 0 | 59 | 0 | 0 | 0 |
| Systems / Networks | ||||||||
| 5200 | Network connectivity | 0 | 1 | 0=Off, 1=On | 1=On | 0 | ||
| 5201 | Get IP address From | 0 | 1 | 0=DHCP, 1=Static | 0=DHCP | 0 | ||
| 5202 | Static IP address (a) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5203 | (b) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5204 | © | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5205 | (d) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5206 | Static Net Worm (a) | 0 | 1 | 0 | 255 | 0 | 255 | 0 |
| 5207 | (b) | 0 | 1 | 0 | 255 | 0 | 255 | 0 |
| 5208 | © | 0 | 1 | 0 | 255 | 0 | 255 | 0 |
| 5209 | (d) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5210 | Static Gateway IP address (a) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5211 | (b) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5212 | © | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5213 | (d) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5214 | Static DNS IP address (a) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5215 | (b) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5216 | © | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5217 | (d) | 0 | 1 | 0 | 255 | 0 | 0 | 0 |
| 5220 | Auto. Restart | 4 | 1 | 0=Off, 1=On | 1=On | 0 | ||
| 5240 | Connect to EvoCloud | 4 | 1 | 0=Off, 1=On | 1=On | 0 | ||
| 5241 | Allow remote control | 4 | 1 | 0=Off, 1=Yes, 2=Time | 0=Off | 0 | ||
| 5242 | Remote control time | 4 | 1 | 1 | 720 | 0 | 72 | h |
| 5290 | Restarting the genset | 4 | 1 | “0=No, 1=Yes, (Automatically reset to 0)” | 0=No | 0 | ||
| Reset | ||||||||
| 5300 | Fan | 0 | 1 | “0=No, 1=Level 1, 2=Level 2, 3=Levels 1 & 2, (Resets automatically to 0)” |
0=No | 0 | ||
| 5301 | temperature | 0 | 1 | “0=No, 1=Level 1, 2=Level 2, 3=Levels 1 & 2, (Resets automatically to 0)” |
0=No | 0 | ||
| 5302 | Extra credit | 0 | 1 | “0=No, 1=Level 1, 2=Level 2, 3=Levels 1 & 2, (Resets automatically to 0)” |
0=No | 0 | ||
| 5303 | Features | 0 | 1 | “0=No, 1=Level 1, 2=Level 2, 3=Levels 1 & 2, (Resets automatically to 0)” |
0=No | 0 | ||
| 5304 | Button lock | 0 | 1 | “0=No, 1=Level 1, 2=Level 2, 3=Levels 1 & 2, (Resets automatically to 0)” |
0=No | 0 | ||
| 5305 | Alarm settings | 0 | 1 | “0=No, 1=Level 1, 2=Level 2, 3=Levels 1 & 2, (Resets automatically to 0)” |
0=No | 0 | ||
| System Information | ||||||||
| 5400 | Current time | 3 | 100 | -2147483647 | 2147483647 | 0 | 1735693200 | Epoch |
| 5401 | (ModBus) | 3 | 100 | 0 | 0 | 0 | ||
| 5410 | Model designation | 0 | 100 | 0 | 0 | |||
| 5411 | Serial number | 0 | 100 | 0 | 0 | |||
| 5412 | Article number | 0 | 100 | 0 | 0 | |||
| 5413 | Programme version DUC | 0 | 100 | 0 | 0 | |||
| 5414 | Bootloader version DUC | 0 | 100 | 0 | 0 | |||
| 5415 | Programme version Display | 0 | 100 | 0 | 0 | |||
| 5416 | Bootloader version Display | 0 | 100 | 0 | 0 | |||
| 5417 | Registration code EvoCloud | 0 | 100 | 0 | 0 | |||
| 5418 | Security code EvoCloud | 0 | 100 | -1 | 65535 | 0 | 0 | |
| 5420 | Database version | 0 | 100 | 0 | 0.5.25 | |||
| 5422 | Inspected | 3 | 100 | -2147483647 | 2147483647 | 0 | Epoch | |
| 5423 | (ModBus) | 3 | 100 | 0 | 0 | |||
| 5424 | Operational | 3 | 100 | -2147483647 | 2147483647 | 0 | Epoch | |
| 5425 | (ModBus) | 3 | 100 | 0 | 0 | |||
| 5430 | MAC address | 0 | 100 | 0 | 0 | |||
| 5431 | IP address | 0 | 100 | 0 | 0 | |||
| 5432 | Fishnet | 0 | 100 | 0 | 0 | |||
| 5433 | Gateway address | 0 | 100 | 0 | 0 | |||
| 5434 | Ethernet link | 3 | 100 | 0=Down, 1=Up | 0=Down | 0 | ||
| 5435 | Connected to the Internet | 3 | 100 | 0=No, 1=Yes | 0=No | 0 | ||
| 5440 | Connected to EvoCloud | 3 | 100 | 0=No, 1=Yes | 0=No | 0 | ||
| 5450 | Alarm type Fans | 0 | 100 | 0=Relay, 1=Taco (A390T and larger units have relay output) | 1=Taco | 0 | ||
| Test | ||||||||
| 5700 | Test mode | 0 | 0 | 0=Off, 1=On | 0=Off | 0 | ||
| 5710 | Dampers | 0 | 0 | 0=Off, 1=On | 0=Off | 0 | ||
| 5711 | Fan speed Supply air | 0 | 0 | 0 | 100 | 0 | 0 | % |
| 5712 | Supply air Fan speed | 0 | 0 | 0 | 20000 | 0 | 0 | rpm |
| 5713 | Fan Supply air Alarm | 0 | 0 | 0=Off, 1=On | 0=Off | 0 | ||
| 5714 | Fan speed Exhaust air | 0 | 0 | 0 | 100 | 0 | 0 | % |
| 5715 | Exhaust air Fan speed | 0 | 0 | 0 | 20000 | 0 | 0 | rpm |
| 5716 | Fan Exhaust air Alarm | 0 | 0 | 0=Off, 1=On | 0=Off | 0 | ||
| 5717 | Output VVX | 0 | 0 | -1 | 100 | -1=100% | 0 | % |
| 5718 | Heat exchanger Speed | 0 | 0 | 0 | 100 | Decimal number | 0 | rpm |
| 5719 | Output Heat | 0 | 0 | 0 | 100 | 0 | 0 | % |
| 5720 | Output Cold | 0 | 0 | 0 | 100 | 0 | 0 | % |
| 5730 | Supply air temperature | 0 | 0 | -50 | 70 | Decimal number | 0 | °C |
| 5731 | Exhaust air temperature | 0 | 0 | -50 | 70 | Decimal number | 0 | °C |
| 5732 | Outdoor air temperature | 0 | 0 | -50 | 70 | Decimal number | 0 | °C |
| 5733 | Return temperature Water | 0 | 0 | -50 | 70 | Decimal number | 0 | °C |
| 5740 | Supply air Pressure | 0 | 0 | 0 | 100 | Decimal number | 0 | % |
| 5741 | Exhaust air Pressure | 0 | 0 | 0 | 100 | Decimal number | 0 | % |
| 5742 | Air quality | 0 | 0 | 0 | 100 | Decimal number | 0 | % |
| 5743 | Extra a/d input 1 | 0 | 0 | 0 | 100 | Decimal number | 0 | % |
| 5744 | Extra a/d entrance 2 | 0 | 0 | 0 | 100 | Decimal number | 0 | % |
| Tidur | ||||||||
| 8xx0 | Available | 4 | 0 | 0=No, 1=Yes | 0=No | 0 | ||
| 8xx1 | Active | 4 | 0 | 0=No, 1=Yes | 1=Yes | 0 | ||
| 8xx2 | Drift mode | 4 | 0 | 0=Off, 1=Save, 2=Comfort, 3=Forced, 4=External 1, 5=External 2, 6=AirQ | 0=Off | 0 | ||
| 8xx3 | Day of the week | 4 | 0 | 0=Monday, 1=Tuesday, 2=Wednesday, 3=Thursday, 4=Friday, 5=Saturday, 6=Sunday, 7=All days, 8=Wednesdays, 9=Wednesdays |
0=Monday | 0 | ||
| 8xx4 | Hour | 4 | 0 | 0 | 23 | 0 | 0 | 0 |
| 8xx5 | minute | 4 | 0 | 0 | 59 | 0 | 0 | 0 |
| xx | number of timers, max 32 pcs | 1 | 32 | Replace xx with the location of the clock | ||||
| Alarm | ||||||||
| 9001 | Active alarms (alarm time 1-32) | 3 | 99 | 0 | 2147483647 | Bit, id from alarm settings, ex. 0×0010h=id 5 | 0 | bit |
| 9002 | (ModBus) (larmid 17-32) | 3 | 99 | ex. 0×0010h=id 21 | 0 | 0 | ||
| 9003 | Active alarms (alarm time 33-64) | 3 | 99 | 0 | 2147483647 | Bit, id from alarm settings, ex. 0×0010h=id 37 | 0 | bit |
| 9004 | (ModBus) (larmid 49-64) | 3 | 99 | ex. 0×0010h=id 53 | 0 | 0 | ||
| 9005 | Clear alarm history | 4 | 0 | 0=No, 1=Yes (automatically reset to 0) | 0=No | 0 | ||
| – | Alarm scheme | Last alarm yy=01, second last yy=02 etc. | ||||||
| 9yy1 | Alarm code | 3 | 0 | 0 | 2147483647 | Id from alarm settings | 0 | 0 |
| 9yy2 | Alarm time | 3 | 0 | 0 | 2147483647 | Latest alert | 0 | Epoch |
| 9yy3 | (ModBus) | 3 | 0 | 0 | 0 | 0 | ||
| 9yy4 | Receipt time | 4 | 0 | 0 | 2147483647 | 0=No Ack, 1=Ack (sets current time), 2=Auto Ack, 3 >= Ack time in Epoch |
0 | Epoch |
| 9yy5 | (ModBus) | 4 | 0 | 0 | 0 | 0 | ||
| yy | number of alarms, max 32 | 1 | 32 | Replace yy with the alarm location | ||||