Go to content

EvoControl Ventilation Touch Display

Language:
en-GB
Models: A100 G3, A110T G3-G4, A170T G2, A200S, A230T, A250S, A390T, A400S, A590T, A600S/T, A900ST G3, A1, A2, M1, M2, R20, R25, R40, R50, R70

7.1.6 Alarm settings

900 - 943. Alarm setting

Alarms can be switched off and in three different categories:

  • Off = Alarm switched off.
  • A-Alarm = Stop of unit (see also emergency alarm), acknowledgement required.
  • B-Alarm = No stop of unit, acknowledgement required.
  • C-Alarm = Non-stop of unit, automatic acknowledgement when fault reset or manual acknowledgement.

Setting of alarm delay.

Alarm codes

  • 1B Communication Display
  • 2C Network, TCP/IP
  • 3C Internet connection
  • 4C Cloud service
  • 5A Fan Supply air
  • 6A Fan Exhaust air
  • 7A Heat exchanger
  • 8A Freeze alarm Return circuit
  • 9A Low supply air temperature
  • 10A Low Exhaust Air Temp
  • 11A Temp sensor Supply air
  • 12A Exhaust air temperature sensor
  • 13A Outdoor air temperature sensor
  • 14A Temp sensor Freeze guard
  • 15B Moisture sensor
  • 16B Pressure value Supply air
  • 17B Exhaust air pressure value
  • 18C Fire
  • 19B High Reheat Temp
  • 23B Communication Stepper motor