6.16 Air quality sensors

  • Connect the air quality sensors to terminals 57 and 61.
  • A 24 Vdc power supply for the air quality sensor is available at terminals 57 and 58.
  • Select air quality sensor in parameter 330.
  • Set the air quality sensor measuring range in parameter 331.
  • Controlling the amount of air with air quality sensors is done via the built-in timer.

See the wiring diagram here.