7.1.3 Additional donors
300 Input A, Drive mode
Plint 1 & 2. Select the operating mode when the input is activated.
301 Entrance A, Order of priority
Prio:
- The order as below if more inputs are active.
- Operating mode:
- Fire function, plinth entrance open.
- Stop, Control panel.
- Stop, plinth entrance open.
- External 2, plinth entrance closed.
- External 1, plinth entrance closed.
- Forced, plinth entrance closed.
- Comfort, plastic entrance closed.
- Spar, platinum input closed.
- Display.
Last input:
- Operating mode is valid until the next command.
302 Switch-off delay
To enable a function, set the value to a number greater than 0. When the input is deactivated, the switch-off delay begins before the system returns to the new operating mode in accordance with parameter 303.
303 Operating mode Return
Return to operating mode after the input has been deactivated.
310 Input B, Operating mode
Plint 3 & 4. Select the operating mode when the input is activated.
311 Entrance B, Order of priority
Prio:
- The order as above if more inputs are active.
Last input:
- Operating mode is valid until the next command.
312 Input B, Switch-off delay
To enable a function, set the value to a number greater than 0. When the input is deactivated, the switch-off delay begins before the system returns to the new operating mode in accordance with parameter 313.
313 Input B, Operating Mode Return
Return to operating mode after the input has been deactivated.
320 Humidity sensors (accessories)
Activation of the connected humidity sensor.
321 Setpoint moisture
Setpoint for humidity control, RF %.
322 Capacity increase
Capacity increase of supply and extract air in % with humidity control.
323 Coupling diff Humidity control
Trigger level below the target value.
324 Control signal VVX for humidity control
Maximum limitation of control signal to rotary heat exchanger in active humidity control. This function minimises the moisture recovery of the heat exchanger.