4.3 Fan

Operating modes 2 and 3 (fan stop) are not available as of software version 5.6

The fan has three different operating modes

  1. Constant operation of the process air fan.
  2. The fan stops when the humidity level falls below the set value. Every 4 hours, the fan starts up and runs for 15 minutes to check the humidity level.
  3. The fan stops when the humidity level falls below the set value. Every 12 hours, the fan starts up and runs for 3 minutes to check the humidity level.

During the time when the fan is stopped, no new values for humidity and temperature are read, this means that the dehumidifier never starts dehumidifying during the stop time.

RD/12/18/24 dehumidifiers

The dehumidifier can be operated in two different capacity modes via the switch on the outside of the dehumidifier.

  • Mode 1 = low.
  • Mode 2 = High.