EvoDry EDC 1.0 Dehumidifier – MPO

Language:
en-GB
Models: PD, PDX, PD+, 6-24P, RCF 12-20 G1

6.1.5 “Settings”

On the PDX model, the “Settings” menu never appears!

Setting a new value:

  • Go to the parameter you want to change with and
  • Pressures  to choose to change the value.
  • Select new value with  and 
  • Pressures  (if the value is not changed, you will return to the selected parameter).
  • Select with  and  “Yes” to confirm or “No.” to keep the old value .
  • Confirm and save by pressing  and you are back to the selected parameter.

Parameters:

Moisture Inst:

  • Set the desired maximum relative humidity in % (setpoint).
  • You can also select “Always Off” and “Always On”.

Hysteresis:

  • Set the desired hysteresis in %.
  • The dehumidifier starts at the setpoint and switches off at the setpoint minus the hysteresis.

*Software versions prior to 1.3.0 have a fixed hysteresis of ± 2%.

Moisture management:

  • Select “RF” or “RF + Temp”.
  • RF:
    Dehumidification starts when the relative humidity of the air exceeds the set value.
  • RF + Temp:
    Dehumidification starts when the relative humidity of the air exceeds the set value at temperatures above +15°C.
    The moisture content is allowed to rise by 1%/°C at temperatures below +15°C before dehumidification starts.
    The function is only active in the temperature range 0-15°C.
    At temperatures below 0°C, the curves continue horizontally, i.e. the moisture content is allowed to be 15% above the set value no matter how cold it gets.

Fan control:

Operating modes 2 and 3 (fan stop) are not available in software version 1.2.0

  • The fan has four different operating modes.
  • Constant operation of the process air fan.
  • Fan stop 1 (T15m/4h) when the moisture content falls below the set value.
    Every 4 hours, the fan starts and runs for 15 minutes to check the moisture content.
  • Fan stop 2 (T3m/12h) when the humidity falls below the set value.
    Every 12 hours, the fan starts and runs for 3 minutes to check the moisture content.
  • Fan stop 3 (T3m/1h) when the moisture content falls below the set value.
    Every hour, the fan switches on and runs for 3 minutes to check the humidity level.

Climate alert:

  • The number of days during which the moisture content may remain above the alarm curve (red) before a climate alarm is triggered.

Alarm curve:

  • The alarm curve is adjustable and runs parallel to the setpoint with an adjustable offset

Maintenance:

  • Number of months between maintenance.
    Cleaning, filter replacement, etc…

Starting sequence:

  • The number of days on which the dehumidifier reduces the setpoint humidity level by 70%.

High temp:

  • Maximum process air temperature.
    3°K hysteresis.

Start delay:

  • The number of minutes during which the humidity level exceeds the set value before the dehumidifier starts dehumidifying.

Hide settings:

  • Hide settings from the “Menu” menu.
  • To adjust settings when they are hidden:
    Gå till raden “Systeminformation” i menyn “Meny” och tryck på  for 10 seconds.

PDX models cannot access the “Settings” menu.

Manufacturer’s instructions:

  • The dehumidifier resets all parameters in the “Settings” menu to their factory defaults.

Back

  • If you press  you will be returned to the “Menu” menu.