6.3.1 Function

If the alarm is active or unacknowledged, the alarm symbol appears at the top of the display and the alarm is added to the alarm list.

A-alarm

  • The dehumidifier is stopped *1.
  • Manual acknowledgement of alarms is required, and faults must be cleared before restart *2.

**1 If Standby mode, parameter 480, is enabled (see function in the parameter list).

**2 To exit Standby mode, the fault must be cleared and acknowledged, then the unit must be Stopped before restarting.

B-alarm

  • The dehumidifier continues to run.
  • Manual acknowledgement of alarms

C-alarm

  • The dehumidifier continues to run.
  • Automatic acknowledgement when alarm returns to normal or manual acknowledgement of alarm.