7.1.6 Alarm settings

900 - 941. Alarm setting.

Alarms can be switched off and in three different categories:

  • Off = Alarm switched off.
  • A-Alarm = Stop of unit (see also emergency alarm), acknowledgement required.
  • B-Alarm = No stop of unit, acknowledgement required.
  • C-Alarm = Non-stop of unit, automatic acknowledgement when fault reset or manual acknowledgement.

Setting of alarm delay.

Alarm codes

  • 1B Communication Display
  • 2C Network, TCP/IP
  • 3C Internet connection
  • 4C Cloud service
  • 5A Fan Process air
  • 6A Fan Rain air
  • 7A Rotor
  • 8A Heater, Low increase
  • 9A Heater, High at off
  • 10B Capacity, dehumidified.
  • 11B RF over risk curve
  • 13A Tempgivare Regluft
  • 14A Temperature sensor Wet air
  • 15A Temp sensor Dry air
  • 17A Humidity sensor, internal
  • 18A Humidity sensor External 1
  • 19A Humidity sensor External 2
  • 20C Fire
  • 21B Pro Air High

Error description Alarm

8A Heater, Low increase

Occurs if dehumidification is ON and wet air temperature is lower än temperatur för regluft + 5.

Possible causes:

  • Broken heater
  • Broken power relay
  • Broken relay on main board
  • If the rotor is very humid, it may take a long time for the temperature to rise
  • Tripped fuse in feeding centre

Adjusting parameter 915 may solve the problem.

Id Text ModBus Level Min Max Text values / ModBus Factory value Unit
914 Heaters, Low increase 4 2 Id 8, 0=Off, 1=A alarm, 2=B alarm, 3=C alarm 1=A alarm
915 Alarm delay, P914 4 2 1 60 10 m

9A Heater, High at off

Occurs if dehumidification is OFF and wet air temperature is higher än temperatur för regluft + 10.
Possible causes:

  • Short circuit in relay contact

10B Capacity, dehumidified.

Occurs if dehumidification is ON for more than 10 days and operation mode is NOT set to CONSTANT mode.

Possible causes:

  • Problems with heaters
  • Problems with the rotor
  • Too small capacity of the dehumidifier for that space (unable to dehumidify)

21B Pro Air High

Occurs if the process air temperature is above 40 degrees.

Possible causes:

  • Leakage from wet air to process air
  • High temperature in dehumidified space