AVC-02 Ventilation

Language:
en-GB
Models: A50S G1, A70T G1–G2, A100S G1–G2, A110T G1–G2, A200S G1, A170T G1, A900ST G1

4.2.2 Emergency

In case of an A-alarm that normally stops the unit and emergency mode activated in parameter 95, the unit's extract air fan continues to run.

  • Supply air fan = Off.
  • Exhaust air fan = On (capacity according to factory settings in each operating mode in %).
  • Heat exchanger = On.
  • Internal electric battery = Off.

The unit does not go into Emergency mode in case of an alarm on the extract air fan.

After the alarm is cancelled, the power to the ventilation unit must be cut off to end the emergency.